Structure Design:
Applications:Aerial, Overhead, Outdoor
Main Features:
1. High quality IEC607948 IEEE1138 standards for designing, testing, and producing with grade A materials available to ensure long-term reliability.
2. Engineering support supervising and providing its own line of accessories hardware.
3. Seal stainless steel tube superior protection to the fiber optical to moisture and extreme environmental conditions such as lightning.
4. To construct OPGW must cut power, resulting in greater loss, thus OPGW must be used in constructing a high-pressure line over 110kv.
5. Apply to the transformation of old lines.
Colors -12 Chromatography:
Technical Parameter:
Typical Design for Single Layer:
Specification |
Fiber Count |
Diameter(mm) |
Weight (kg/km) |
RTS(KN) |
Short Circuit(KA2s) |
OPGW-80(82.3;46.8) |
24 |
11.9 |
504 |
82.3 |
46.8 |
OPGW-70(54.0;8.4) |
24 |
11 |
432 |
70.1 |
33.9 |
OPGW-80(84.6;46.7) |
48 |
12.1 |
514 |
84.6 |
46.7 |
Typical Design for Double Layer:
Specification |
Fiber Count |
Diameter(mm) |
Weight (kg/km) |
RTS(KN) |
Short Circuit(KA2s) |
OPGW-143(87.9;176.9) |
36 |
15.9 |
617 |
87.9 |
176.9 |
Remarks:
Detail requirements need to be sent to us for cable design and price calculation. Below requirements are a must:
A, Power transmission line voltage level
B, fiber count
C, Cable structure drawing & diameter
D, Tensile strength
F, Short circuit capacity
Standard:
ITU-TG.652 |
Characteristics of a single mode optical fiber. |
ITU-TG.655 |
Characteristics of a non-zero dispersion -shifted single mode fibers optical. |
EIA/TIA598 B |
Col code of fiber optic cables. |
IEC 60794-4-10 |
Aerial optical cables along electrical power lines-family specification for OPGW. |
IEC 60794-1-2 |
Optical fiber cables -part test procedures. |
IEEE1138-2009 |
IEEE Standard for testing and performance for optical ground wire for use on electric utility power lines. |
IEC 61232 |
Aluminum -Clad steel wire for electrical purposes. |
IEC60104 |
Aluminum magnesium silicon alloy wire for overhead line conductors. |
IEC 6108 |
Round wire concentric lay overhead electrical stranded conductors. |
Quality Control:
GL FIBER' OPGW cable is mainly divided into: central-type stainless steel tube OPGW, stranded-type stainless steel tube OPGW, al-covered stainless steel tube OPGW, aluminum tube OPGW, lightning resistant central stainless steel tube OPGW with compressed wires and OPPC.
All the OPGW cable supplied from GL FIBER will be 100% tested before shipping, There are different general test series to assure the quality of OPGW cable, Such as:
Type test
Type test may be waived by submitting makerʼs certificate of the similar product performed in an internationally acknowledged independent test organization or laboratory. If type test should be performed, it will be carried out according to an extra type test procedure reached to an agreement between purchaser and manufacturer.
Routine test
The optical attenuation coefficient on all production cable lengths is measured according to IEC 60793-1-CIC (Back-scattering technique, OTDR). Standard single-mode fibers are measured at 1310nm and at 1550nm. Non-zero dispersion shifted single‒mode (NZDS) fibers are measured at 1550nm.
Factory test
Factory acceptance test is carried out on two samples per order in the presence of the customer or his representative. The requirements for quality characteristics are determined by relevant standards and agreed quality plans.
Quality Control - Test Equipment and Standard:
Feedback:
In order to meet the world’s highest quality standards, we continuously monitor feedback from our customers. For comments and suggestions, please, contact us, Email: [email protected].