OPGW Optical Cable is primarily used by the electric utility industry, placed in the secure topmost position of the transmission line where it “shields” the all-important conductors from lightning while providing a telecommunications path for internal as well as third party communications. Optical Ground Wire is a dual functioning cable, meaning it serves two purposes. It is designed to replace traditional static / shield / earth wires on overhead transmission lines with the added benefit of containing optical fibers which can be used for telecommunications purposes.
Stranded stainless steel tube OPGW, Central Al-covered stainless steel tube OPGW, Aluminum PBT Loose Tube OPGW are three typical designs of OPGW optical cables.
The Stranded Optical Ground Wire (OPGW)
Structure: Double or three layers of aluminum clad steel wires(ACS) or mix ACS wires and aluminum alloy wires.
Application: Aerial , Overhead , Outdoor
Typical design for Double Layer:
Specification | Fiber Count | Diameter(mm) | Weight (kg/km) | RTS(KN) | Short Circuit (KA2s) |
OPGW-89[55.4;62.9] | 24 | 12.6 | 381 | 55.4 | 62.9 |
OPGW-110[90.0;86.9] | 24 | 14 | 600 | 90 | 86.9 |
OPGW-104[64.6;85.6] | 28 | 13.6 | 441 | 64.6 | 85.6 |
OPGW-127[79.0;129.5] | 36 | 15 | 537 | 79 | 129.5 |
OPGW-137[85.0;148.5] | 36 | 15.6 | 575 | 85 | 148.5 |
OPGW-145[98.6;162.3] | 48 | 16 | 719 | 98.6 | 162.3 |
Typical design for Three Layer:
Specification | Fiber Count | Diameter(mm) | Weight (kg/km) | RTS(KN) | Short Circuit (KA2s) | ||||
OPGW-232[343.0;191.4] | 28 | 20.15 | 1696 | 343 | 191.4 | ||||
OPGW-254[116.5;554.6] | 36 | 21 | 889 | 116.5 | 554.6 | ||||
OPGW-347[366.9;687.7] | 48 | 24.7 | 2157 | 366.9 | 687.7 | ||||
OPGW-282[358.7;372.1] | 96 | 22.5 | 1938 | 358.7 | 372.1 |
Central AL-covered Stainless Steel Tube OPGW
Structure: central AL-covered steel tube is surrounded by single or double layers of aluminum clad steel wires(ACS) or mix ACS wires and aluminum alloy wires.AL-covered Stainless Steel Tube design increases the cross section of aluminum.
Application: Aerial , Overhead , Outdoor.
Typical Design for Single Layer
Specification | Fiber Count | Diameter(mm) | Weight (kg/km) | RTS(KN) | Short Circuit(KA2s) |
OPGW-80(82.3;46.8) | 24 | 11.9 | 504 | 82.3 | 46.8 |
OPGW-70(54.0;8.4) | 24 | 11 | 432 | 70.1 | 33.9 |
OPGW-80(84.6;46.7) | 48 | 12.1 | 514 | 84.6 | 46.7 |
Typical Design for Double Layer
Specification | Fiber Count | Diameter(mm) | Weight (kg/km) | RTS(KN) | Short Circuit(KA2s) |
OPGW-143(87.9;176.9) | 36 | 15.9 | 617 | 87.9 | 176.9 |
Structure: single or double layers of aluminum clad steel wires(ACS) or mix ACS wires and aluminum alloy wires.
Application: Aerial , Overhead , Outdoor
Technical Parameter:
Specification | Fiber Count | Diameter(mm) | Weight (kg/km) | RTS(KN) | Short Circuit(KA2s) |
OPGW-113(87.9;176.9) | 48 | 14.8 | 600 | 70.1 | 33.9 |
OPGW-70(81;41) | 24 | 12 | 500 | 81 | 41 |
OPGW-66 (79;36) | 36 | 11.8 | 484 | 79 | 36 |
OPGW-77 (72;36) | 36 | 12.7 | 503 | 72 | 67 |